Frequency Converter

Marine Frequency Converter/Shore Power Supply

BWFCS Marine Frequency Converter/Shore Power Supply (60kVA ~4000kVA)

Marine-Frequency-ConverterShore-
  • Why Marine Frequency Converter
  • There are a growing number of luxury cruise liners and fast car carrying vessels calling at international ports and naval vessels berthing at foreign locations.  Many of the port and harbour operators are now offering vessels the opportunity to “plug into”the local city power supply grid on the dockside so the vessel can turn off its engines while at port. Here there is the problem, many countries have their own local power distribution grid voltages, the American continent has a frequency of 60Hz and most of the other countries of the world have a power distribution frequency of 50Hz.
  • When a vessel berths in a port the propulsion engines are turned off but would normally continue to run its diesel engine driven generators to power all of the on board auxiliaries such as air conditioning, heating, lighting, battery charging, communications center water pumps and other utility services. The auxiliary power diesel generators produce noise; vibrations; exhaust smoke; air pollution; toxic gases; and CO2 emissions, as well as consume vast amounts of unpleasant smelling diesel fuel. They incur costly maintenance and the inevitable need for replacement parts as necessary for all internal combustion engines.
  • BWPS shore frequency converters offer a solution to this issue. By shutting down the vessel’s engine driven auxiliary power generators and connecting to our shore to ship frequency changers there is no smell, barely any audible noise to disturb passengers or neighbouring vessel on board personnel, no vibration smoke or fumes, no CO2 emissions or costly diesel fuel or oil.
  • These fixed shore power frequency converters are designed for use on the public supply grid networks of 50Hz or 60Hz with 3 phase standard input voltages of 208V, 400V, 415V,460V or 575V. The output voltage and frequency will be according to the needs of the ship with voltages and frequencies similar to the input.
  • BWPS shore power converter can be manufactured in sizes of 60kVA to 4000kVA in an indoors type of enclosure for installation in a substation or power distribution room. We can also supply the shore power converters in an all-weather outdoor enclosure which is able to withstand the harshest environmental condition for installing on the dockside or mooring berth.
  • The shore frequency converters provide a galvanic isolation between city grid power pick up point and the on board vessel power distribution network. The converters will regulate and condition the dockside power and will eliminate spikes, dips and other voltage surges and instability problems often encountered on feeder networks connecting simultaneously to a number of vessels.

Item

Specifications

60kVA

100kVA

150kVA

200kVA

250kVA

300kVA

 

Working

Condition

Environment

Ambient temperature: -10℃~+45℃,Relative humidity: 0~95%

Protection class

Indoor type:IP32

Cooling mode

Indoor type: Forced air cooling

Sea level

Continuous output of rated power below 1000m,derating for use more than 1000 meters

 

 

Input

Input voltage

Different input voltage levels can be customized according to customer requirements

Input frequency

50Hz (±10 %) or 60Hz (±10 %)

Input system

3 Phase 3 Wire(Delta )or 3 Phase 4  Wire(Yye)

Rectifier mode

6 Pulse rectifier

Input factor

6 Pulse rectifier ≥ 0.90

Current total harmonic

6 Pulse rectifier THDi ≤35% (100%  load)

 

Output

 

 

 

 

 

 

 

 

 

 

 

 

 

output voltage

440V(Different output voltage levels can be customized according to customer requirements)

Rated current

79A

131A

197A

262A

328A

394A

Output system

3 Phase 3 Wire(Delta )or 3 Phase 4  Wire(Yye)

 

Voltage regulation

Static state ≤0.5V

Dynamic state ≤±1% (0 ~ 100% of ladder type load )

When sudden increase/decrease of 100% rated load the output voltage sags and swells ≤±10%( restore to the rated output voltage within 84ms)

Rated frequency

60Hz or 50Hz or 400 Hz (Accuracy is 0.01)

Frequency stability

≤0.01% (0 ~ 100% load change output frequency is constant)

 

Inverter power overload capacity

Rated output current of 125% is 1 minute

150% rated output current signal alarm, cut off the output, and keep the error signal

Can withstand the 3 times of the rated output current instantaneous peak current shock, when more than 3 times of the rated output current instantaneous peak current frequency conversion power Reverse time trip protection

(Reverse time tripping means the greater the current, the shorter the tripping protection time)

Output voltage total harmonic

THDu≤1% (No load or linear load)

Voltage imbalance

Less than1%

Output voltage

phase Angle

120°(±0.1°)

Overall efficiency

≥95% (100% rated load)

 

 

Structural

 

Performance

Inverter main circuit topology

The three-phase full-bridge inverter circuit is composed of PrimerPACK series high-power IGBT power switch module by INFINEON or IPM intelligent power module by SEMIKRON

Modulation mode

SVPWM space vector pulse width modulation method

Voltage control mode

instantaneous output voltage waveform control

Switching frequency

3.6KHZ~6KHZ

PWM drive mode

5MHZ fiber driven transmission

Master processor

TMS320F28335,150MHZ

Sine filter way

third order sinusoidal filter at the output end of the inverter

Touch screen

10.4″ , 1024*600 (High definition )

 

Protection

 

 

 

Trip protection

Input power occurs missing phase, under voltage, over voltage, over current, short circuit, dc bus bar over voltage when the frequency converter power supply trip protection(Protection valve value set arbitrary)

Output power occurs missing phase, under voltage, over voltage, over current, short circuit, reverse power when the frequency conversion power trip protection(Protection valve value set arbitrary)

When transformer, sine filter, rectifier, power module exceeds the normal operating temperature when the frequency converter power tripping protection (temperature value can be set arbitrarily)

Output current

Instantaneous peak output current limit

 

 

 

Other

Withstand voltage

Low voltage: 2500V/AC, 1 minute, no breakdown and ignition (leakage current < 10mA); High voltage:

42KV/AC, 1 minute, no breakdown ignition phenomenon.

Cold insulation resistance

≥100MΩ (Measured with a 1000V megohm meter)

The noise

≤55dB(A)

Dimensions of Indoor type(mm

800(L)*670(

W) *1100(H)

900(L)*700(

W) *1200(H)

1100(L)*900(

W) *1500(H)

1200(L)*1000(

W) *1800(H)

1500 (L)*1500 (W)*1800 (H)

Weight(kg)

600kg

700kg

1200kg

1500kg

1800kg

2200kg

Colour

 Indoor type : Standard color number7032


Item

Specifications

400kVA

630kVA

800kVA

1000kVA

1250kVA

1600kVA

2000kVA

3000kVA

4000kVA

Working

Condition

Environment

Ambient temperature: -10℃~+45℃,Relative humidity: 0~95%

Protection class

Container type:IP65,Indoor type:IP32

Cooling mode

Container type: All air conditioning cooling,Indoor type: Forced air cooling

Sea level

Continuous output of rated power below 1000m,More than 1000 meters derated use

 

 

Input

Input voltage

Different input voltage levels can be customized according to customer requirements

Input frequency

50Hz (±10 %) or 60Hz (±10 %)

Input phase

3 Phase 3 Wire(Delta )or 3 Phase 4  Wire(Yye)

Rectifier mode

6 Pulse rectifier or 12 Pulse rectifier or PWM rectifier

Input factor

6 Pulse rectifier ≥ 0.90,12 Pulse rectifier ≥ 0.96,PWM rectifier ≥ 0.99

Current total harmonic

6 Pulse rectifier THDi ≤35%,12 Pulse rectifier THDi ≤15%,PWM rectifier THDi ≤5% (100% rated load)

 

Output

 

 

 

 

 

 

 

 

 

 

 

 

 

output voltage

Different output voltage levels can be customized according to customer requirements

Rated  current

525A/440V

826A/440V

1050A/440V

1312A/440V

1640A/440V

109A/6.6KV

2100A/440V

140A/6.6KV

2624A/440V

175A/6.6KV

3937A/440V

262A/6.6KV

5249A/440V

350A/6.6KV

Output system

3 Phase 3 Wire(Delta )or 3 Phase 4  Wire(Yye)

 

Voltage regulation

Static state ≤0.5V

Dynamic state ≤±1% (0 ~ 100% of ladder type load )

When sudden increase/decrease of 100% rated load the output voltage sags and swells ≤±3%(Return to the rated output voltage at 0.5 base cycle less than 8 ms)

Rated output frequency

60Hz or 50Hz or 400 Hz (Accuracy is 0.01)

Frequency stability

≤0.01% (0 ~ 100% load change output frequency is constant)

 

Inverter power overload capacity

Rated output current of 125% is 1 minute

150% rated output current signal alarm, cut off the output, and keep the error signal

Can withstand the 3 times of the rated output current instantaneous peak current shock, when more than 3 times of the rated output current instantaneous peak current frequency conversion power Reverse time trip protection

(Reverse time tripping means the greater the current, the shorter the tripping protection time)

Output voltage total harmonic

THDu≤1% (No load or linear load)

Output voltage imbalance

Less than1%

Output voltage

phase Angle

120°(±0.1°)

Overall efficiency

≥95% (100% rated load)

 

 

Structural

 

Performance

Inverter main circuit topology

The three-phase full-bridge inverter circuit is composed of PrimerPACK series high-power IGBT power switch module by INFINEON or IPM intelligent power module by SEMIKRON

Modulation mode

SVPWM space vector pulse width modulation method

Voltage control mode

instantaneous output voltage waveform control

Switching frequency

3.6KHZ~6KHZ

PWM drive mode

5MHZ fiber driven transmission

Master processor

TMS320F28335,150MHZ

Sine filter way

third order sinusoidal filter at the output end of the inverter

Touch screen

10.4″ , 1024*600 (High definition )

 

Protection

 

 

 

Trip protection

Input power occurs missing phase, under voltage, over voltage, over current, short circuit, dc bus bar over voltage when the frequency converter power supply trip protection(Protection valve value set arbitrary)

Output power occurs missing phase, under voltage, over voltage, over current, short circuit, reverse power when the frequency conversion power trip protection(Protection valve value set arbitrary)

When transformer, sine filter, rectifier, power module exceeds the normal operating temperature when the frequency converter power tripping protection (temperature value can be set arbitrarily)

Output current

Instantaneous peak output current limit

 

 

 

Other

 

Withstand voltage

Low voltage: 2500V/AC, 1 minute, no breakdown and ignition (leakage current < 10mA); High voltage:

42KV/AC, 1 minute, no breakdown ignition phenomenon.

Cold insulation resistance

≥100MΩ (Measured with a 1000V megohm meter)

The noise

≤55dB(A)

Dimensions of container type(mm

5100(L)*2438( W)*2896(H)

6058(L)*2438( W)*2896(H)

9000(L)*2438( W)*2896(H)

12192(L)*2438(W)*2896(H)

Weight(Ton)

4.5T

5T

6T

6.5T

8T

9T

12T

18T

25T

Dimensions of Indoor type(mm

3200(L)*1500(W) *2200(H)

4300(L)*1500(W) *2300 (H)

9400 (L)*1500(W)*2300

(H)

12000 (L)*1500 (W)*2300(H)

Weight(Ton)

2.5T

3T

3.5T

4T

5T

6T

8T

12T

19T

Colour

container type : sky blue; Indoor type : Standard color number7032